UIO- 24DI Modbus Module
UIO- 24DI Modbus Module Original price was: ₹8,000.00.Current price is: ₹7,000.00.
Back to products
Voltage Source Simulator 0-10V (USS10V24V-D)
Voltage Source Simulator 0-10V (USS10V24V-D) Original price was: ₹7,000.00.Current price is: ₹5,000.00.

UIO- 48DI Modbus Module

Original price was: ₹12,000.00.Current price is: ₹10,000.00.

Product Features
● 24 V DC Input Supply
● 48 PNP Digital Input
● Modbus RS-485 Protocol Interface
● Convenient address selection rotatory switch from 1 – 99 Address
● Dimension – 110 mm x 150 mm x 85 mm

Description

Features

● Four Channel 0 ~ 20mA 12 bit Resolution ADC
● Modbus RS-485 Protocol Interface.
● Individual Channel offset calibration
● Resolution at 0.005 mA
● Convenient address selection rotatory switch from 1 – 99 Address
● Complete range of baud rate settings supported
● Sensor open indication
● Suitable for both Din Rail and Wall Mountable
● Product Dimensions 110mm x 50mm x 55mm (L x W x H)

Default Mode Switch

Default mode is handy when the serial communication setting are forgotten.
Setting the Address switch to 00 will put the device in default mode
Address Set to 00 - Default mode ON
– Slave Address – 1, Baud 19200, 8N1
Address Set to non 00 - Default mode OFF
– As per the saved configuration values.
Note:
No parameter selection is changed just by entering the default mode. All the parameters
remains same including the communication settings unless changed by the master or if there is a
corruption in data error indicated in normal mode the device will try to recover to Factory settings.
This mode can be used to read the present settings and/or change the settings
Sensor Open indication
If Channel 1 or 2 Sensor is not connected value is read as 0.0 mA and corresponding
Discrete Input bit is set.
Diagnostics
Tx LED - Quick Blink Indicates Tx Data in Normal operation
Rx LED - Quick Blink Indicates Rx Data in Normal operation
Power LED - Power Supply Status

Supported Modbus Function Codes

02 – Read Discrete Inputs
03 – Read Holding Registers
04 – Read Input Registers
06 – Write Single Register
16 – Write Multiple Registers

Discrete Inputs (Read Only)

0x1.1 (1.1)
– Unused
0x1.2 (1.2)
– Unused
0x1.3 (1.3)
– Channel 1 Sensor Status.
1 indicates Sensor Open 0 indicates Working
0x1.4 (1.4)
– Channel 2 Sensor Status.
1 indicates Sensor Open 0 indicates Working
0x1.5 (1.5)
– Channel 1 low value alarm status.
1 indicates alarm is on due to low value / 0 indicates value is with in
normal range
0x1.6 (1.6)
– Channel 1 high value alarm status.
1 indicates alarm is on due to high value / 0 indicates value is with in
normal range
0x1.7 (1.7)
– Channel 2 low value alarm status.
1 indicates alarm is on due to low value / 0 indicates value is with in
normal range
0x1.8 (1.8)
– Channel 2 high value alarm status.
1 indicates alarm is on due to high value / 0 indicates value is with in
normal range