Skip to content

Isolated Analog Signal Converter 10V - 10V

Isolated Analog Signal Converter 10V - 10V AC-10V-10V Datasheet pdf

The AC-10V-10V is an industrial precision analog signal conditioner and isolator engineered to provide 1:1 galvanic isolation for standard 0–10V DC voltage loops. Featuring a pure linear amplifier architecture with zero PWM conversion and zero digital reconstruction, it preserves original analog waveform fidelity with an ultra-fast response time of less than 1 ms and exceptionally low output ripple noise (< ±0.1%). With an ultra-high galvanic isolation barrier of 4.25 kV RMS between input and output, it breaks severe ground loops, protects expensive PLC/DCS analog input channels from common-mode voltage spikes, and eliminates electrical interference across noisy industrial automation environments.

Product image

Key Features

  • 0–10V DC input to 0–10V DC output linear signal conversion
  • 4.25 kV RMS galvanic isolation between input and output
  • 1.5 kV RMS isolation between input and auxiliary power
  • Ultra-fast response time (< 1 ms) for real-time process control
  • Low output ripple noise (< ±0.1%) with ±0.2% full-scale accuracy
  • Pure analog linear amplifier topology with zero digital sampling delay
  • Front-panel multi-turn Zero and Span calibration potentiometers
  • 24V DC auxiliary power supply (18V to 30V DC operating range)
  • Power status LED indicator (PWR)
  • Compact 22 mm DIN rail and wall mountable enclosure
  • Dimensions: 100 mm × 76 mm × 22 mm

Ordering Information

Product Code Description
AC-10V-10V Isolated Analog Signal Converter 0–10V to 0–10V DC (24V DC, 4.25kV Isolation)
AC-420-420 Signal Isolator 4–20mA to 4–20mA Current Loop Isolator
AC-20mA-2 Isolated 20mA Splitter (1 In, 2 Out)
AC-300V-10V Isolated High Voltage Converter 300V DC to 0–10V DC
USS10V24V-D Voltage Source Simulator 0–10V with Digital Display
SPD-24V-DC Surge Protection Device 24V DC SPD

Applications

  • PLC & DCS Analog Channel Protection: Breaks electrical ground loops between field sensors, motor drives, and central automation controllers.
  • VFD & Inverter Analog Control: Safely routes 0–10V speed reference commands from PLCs to variable frequency drives in electrically noisy environments.
  • Building Management Systems (BMS): Interfacing isolated 0–10V damper actuators, valve positioners, and HVAC controllers.
  • OEM Test Benches & Data Acquisition: Clean, high-fidelity voltage buffer for multichannel DAQ cards with complete transient isolation.
  • Industrial Automation & Process Control: Reliable signal interfacing across long cable runs between separate buildings or power domains.

Specifications

Parameter Value
Mounting Type 35 mm DIN Rail & Wall Mounting
Dimensions 100 mm x 76 mm x 22 mm (L x H x W)
Weight 100 g
Enclosure Material Industrial Grade ABS
Operating Temperature 0 °C to +50 °C (Industrial: -10 °C to +60 °C)
Storage Temperature -40 °C to +85 °C
Relative Humidity 5% to 95% RH (non-condensing)

Electrical Specifications

Parameter Specification
Power Supply Voltage 24V DC \(\pm 25\%\) (18V to 30V DC)
Operating Current 100 mA @ 24V DC
Input Signal Range 0.00 V to 10.00 V DC
Output Signal Range 0.00 V to 10.00 V DC (Load \(\ge 2\,\text{k}\Omega\))
Conversion Accuracy \(\pm 0.2\%\) of Full Scale @ 25 °C (max \(\pm 0.5\%\))
Output Ripple Noise \(< \pm 0.1\%\) of Full Scale
Response Time \(< 1\text{ ms}\) (< 1 milliSec)
Temperature Drift \(< 100\text{ ppm} / \text{°C}\)
Status Indication Power LED ON (PWR)
Field Calibration Front-panel multi-turn Zero and Span trimpots

Isolation & Protection Specifications

Parameter Value Standard / Notes
Galvanic Isolation (Input to Output) 4,250 V RMS (4.25 kV) Optical & magnetic isolation barrier (1 min)
Galvanic Isolation (Input to Aux. Power) 1,500 V RMS (1.5 kV) Continuous dielectric isolation
Output to Aux. Supply Shared Common Ground Non-isolated reference ground
Reverse Polarity Protection Integrated Protects internal circuitry against reverse DC supply wiring
Transient Clamping 600W TVS Surge and spike suppression across all ports

Functional Isolation Architecture & Dynamic Response

The pure linear analog architecture provides true continuous signal isolation without quantization stepping or switching ripples.

Galvanic isolation functional diagram

Oscilloscope Dynamic Waveform Verification

Oscilloscope measurement verifying that the isolated output signal (Channel 2) reproduces the input waveform (Channel 1) with sub-millisecond response latency (< 1 ms) and clean sinusoidal tracking:

Oscilloscope dynamic waveform

Mechanical Dimensions

Mechanical dimensions

Terminal Details & Wiring

Wiring diagram

Connection Pinouts

Terminal Block Pin Label Signal Description
Input Terminals 18 18 + Input (+) 0–10V DC Analog Input (+)
(Bottom Block) A2 A2 - Input (-) Analog Input Ground Return (-)
– NC Unused Reserved / Not Connected
– NC Unused Reserved / Not Connected
Output Terminals 15 15 OP+ Output (+) Calibrated 0–10V DC Analog Output (+)
(Top Block) 26 26 OP- Output (-) Analog Output Ground Return (-)
Power Terminals A1 A1 V+ +24V DC Auxiliary Power Supply Input (+24V DC)
(Top Block) 25 25 GND Power 0V Auxiliary Power Supply Ground Return

Available Variants & Configurations

The Veawe Precision Analog Isolator family is available in standardized and custom input/output configurations:

Input Output Input Output Input Output
Signal HV Transducer
0–20 mA 0–20mA, 4–20mA, 0–10V, ±10V 30V DC 0–20mA, 4–20mA, 0–10V Pt100 0–20mA, 4–20mA, 0–10V
4–20 mA 0–20mA, 4–20mA, 0–10V, ±10V 70V DC 0–20mA, 4–20mA, 0–10V Pt1000 0–20mA, 4–20mA, 0–10V
0–10 V DC 0–20mA, 4–20mA, 0–10V, ±10V 100V DC 0–20mA, 4–20mA, 0–10V K type 0–20mA, 4–20mA, 0–10V
0–5 V DC 0–20mA, 4–20mA, 0–10V, ±10V 150V DC 0–20mA, 4–20mA, 0–10V J type 0–20mA, 4–20mA, 0–10V
75 mV DC 0–20mA, 4–20mA, 0–10V, ±10V 300V / ±300V DC 0–20mA, 4–20mA, 0–10V Resistance 0–20mA, 4–20mA, 0–10V
±75 mV DC 0–20mA, 4–20mA, 0–10V, ±10V 350V DC 0–20mA, 4–20mA, 0–10V — —
— — 100V AC 0–20mA, 4–20mA, 0–10V — —
— — 5A AC (CT) 0–20mA, 4–20mA, 0–10V — —

LED Indications and Diagnostics

LED Color Status Description
PWR Green ON Auxiliary 24V DC operating power connected and regulated

Revision History

Revision Date Description of Change
Rev 1.0 2026-09-09 Initial datasheet release

Get the latest version of this datasheet : click here..

Support

Website: www.veawe.io

Email: info@veawe.io