Isolated Analog Signal Converter 10V - 10V
The AC-10V-10V is an industrial precision analog signal conditioner and isolator engineered to provide 1:1 galvanic isolation for standard 0–10V DC voltage loops. Featuring a pure linear amplifier architecture with zero PWM conversion and zero digital reconstruction, it preserves original analog waveform fidelity with an ultra-fast response time of less than 1 ms and exceptionally low output ripple noise (< ±0.1%). With an ultra-high galvanic isolation barrier of 4.25 kV RMS between input and output, it breaks severe ground loops, protects expensive PLC/DCS analog input channels from common-mode voltage spikes, and eliminates electrical interference across noisy industrial automation environments.

Key Features
- 0–10V DC input to 0–10V DC output linear signal conversion
- 4.25 kV RMS galvanic isolation between input and output
- 1.5 kV RMS isolation between input and auxiliary power
- Ultra-fast response time (< 1 ms) for real-time process control
- Low output ripple noise (< ±0.1%) with ±0.2% full-scale accuracy
- Pure analog linear amplifier topology with zero digital sampling delay
- Front-panel multi-turn Zero and Span calibration potentiometers
- 24V DC auxiliary power supply (18V to 30V DC operating range)
- Power status LED indicator (
PWR) - Compact 22 mm DIN rail and wall mountable enclosure
- Dimensions: 100 mm × 76 mm × 22 mm
Ordering Information
| Product Code | Description |
|---|---|
| AC-10V-10V | Isolated Analog Signal Converter 0–10V to 0–10V DC (24V DC, 4.25kV Isolation) |
| AC-420-420 | Signal Isolator 4–20mA to 4–20mA Current Loop Isolator |
| AC-20mA-2 | Isolated 20mA Splitter (1 In, 2 Out) |
| AC-300V-10V | Isolated High Voltage Converter 300V DC to 0–10V DC |
| USS10V24V-D | Voltage Source Simulator 0–10V with Digital Display |
| SPD-24V-DC | Surge Protection Device 24V DC SPD |
Applications
- PLC & DCS Analog Channel Protection: Breaks electrical ground loops between field sensors, motor drives, and central automation controllers.
- VFD & Inverter Analog Control: Safely routes 0–10V speed reference commands from PLCs to variable frequency drives in electrically noisy environments.
- Building Management Systems (BMS): Interfacing isolated 0–10V damper actuators, valve positioners, and HVAC controllers.
- OEM Test Benches & Data Acquisition: Clean, high-fidelity voltage buffer for multichannel DAQ cards with complete transient isolation.
- Industrial Automation & Process Control: Reliable signal interfacing across long cable runs between separate buildings or power domains.
Specifications
| Parameter | Value |
|---|---|
| Mounting Type | 35 mm DIN Rail & Wall Mounting |
| Dimensions | 100 mm x 76 mm x 22 mm (L x H x W) |
| Weight | 100 g |
| Enclosure Material | Industrial Grade ABS |
| Operating Temperature | 0 °C to +50 °C (Industrial: -10 °C to +60 °C) |
| Storage Temperature | -40 °C to +85 °C |
| Relative Humidity | 5% to 95% RH (non-condensing) |
Electrical Specifications
| Parameter | Specification |
|---|---|
| Power Supply Voltage | 24V DC \(\pm 25\%\) (18V to 30V DC) |
| Operating Current | 100 mA @ 24V DC |
| Input Signal Range | 0.00 V to 10.00 V DC |
| Output Signal Range | 0.00 V to 10.00 V DC (Load \(\ge 2\,\text{k}\Omega\)) |
| Conversion Accuracy | \(\pm 0.2\%\) of Full Scale @ 25 °C (max \(\pm 0.5\%\)) |
| Output Ripple Noise | \(< \pm 0.1\%\) of Full Scale |
| Response Time | \(< 1\text{ ms}\) (< 1 milliSec) |
| Temperature Drift | \(< 100\text{ ppm} / \text{°C}\) |
| Status Indication | Power LED ON (PWR) |
| Field Calibration | Front-panel multi-turn Zero and Span trimpots |
Isolation & Protection Specifications
| Parameter | Value | Standard / Notes |
|---|---|---|
| Galvanic Isolation (Input to Output) | 4,250 V RMS (4.25 kV) | Optical & magnetic isolation barrier (1 min) |
| Galvanic Isolation (Input to Aux. Power) | 1,500 V RMS (1.5 kV) | Continuous dielectric isolation |
| Output to Aux. Supply | Shared Common Ground | Non-isolated reference ground |
| Reverse Polarity Protection | Integrated | Protects internal circuitry against reverse DC supply wiring |
| Transient Clamping | 600W TVS | Surge and spike suppression across all ports |
Functional Isolation Architecture & Dynamic Response
The pure linear analog architecture provides true continuous signal isolation without quantization stepping or switching ripples.

Oscilloscope Dynamic Waveform Verification
Oscilloscope measurement verifying that the isolated output signal (Channel 2) reproduces the input waveform (Channel 1) with sub-millisecond response latency (< 1 ms) and clean sinusoidal tracking:

Mechanical Dimensions

Terminal Details & Wiring

Connection Pinouts
| Terminal Block | Pin | Label | Signal | Description |
|---|---|---|---|---|
| Input Terminals | 18 | 18 + | Input (+) | 0–10V DC Analog Input (+) |
| (Bottom Block) | A2 | A2 - | Input (-) | Analog Input Ground Return (-) |
| – | NC | Unused | Reserved / Not Connected | |
| – | NC | Unused | Reserved / Not Connected | |
| Output Terminals | 15 | 15 OP+ | Output (+) | Calibrated 0–10V DC Analog Output (+) |
| (Top Block) | 26 | 26 OP- | Output (-) | Analog Output Ground Return (-) |
| Power Terminals | A1 | A1 V+ | +24V DC | Auxiliary Power Supply Input (+24V DC) |
| (Top Block) | 25 | 25 GND | Power 0V | Auxiliary Power Supply Ground Return |
Available Variants & Configurations
The Veawe Precision Analog Isolator family is available in standardized and custom input/output configurations:
| Input | Output | Input | Output | Input | Output |
|---|---|---|---|---|---|
| Signal | HV | Transducer | |||
| 0–20 mA | 0–20mA, 4–20mA, 0–10V, ±10V | 30V DC | 0–20mA, 4–20mA, 0–10V | Pt100 | 0–20mA, 4–20mA, 0–10V |
| 4–20 mA | 0–20mA, 4–20mA, 0–10V, ±10V | 70V DC | 0–20mA, 4–20mA, 0–10V | Pt1000 | 0–20mA, 4–20mA, 0–10V |
| 0–10 V DC | 0–20mA, 4–20mA, 0–10V, ±10V | 100V DC | 0–20mA, 4–20mA, 0–10V | K type | 0–20mA, 4–20mA, 0–10V |
| 0–5 V DC | 0–20mA, 4–20mA, 0–10V, ±10V | 150V DC | 0–20mA, 4–20mA, 0–10V | J type | 0–20mA, 4–20mA, 0–10V |
| 75 mV DC | 0–20mA, 4–20mA, 0–10V, ±10V | 300V / ±300V DC | 0–20mA, 4–20mA, 0–10V | Resistance | 0–20mA, 4–20mA, 0–10V |
| ±75 mV DC | 0–20mA, 4–20mA, 0–10V, ±10V | 350V DC | 0–20mA, 4–20mA, 0–10V | — | — |
| — | — | 100V AC | 0–20mA, 4–20mA, 0–10V | — | — |
| — | — | 5A AC (CT) | 0–20mA, 4–20mA, 0–10V | — | — |
LED Indications and Diagnostics
| LED | Color | Status | Description |
|---|---|---|---|
| PWR | Green | ON | Auxiliary 24V DC operating power connected and regulated |
Revision History
| Revision | Date | Description of Change |
|---|---|---|
| Rev 1.0 | 2026-09-09 | Initial datasheet release |
Get the latest version of this datasheet : click here..
Support
Website: www.veawe.io
Email: info@veawe.io